Congratulations on selecting this quality Aer-Max system.
Important: Please read all instructions before assembling and installing the Aer-Max system. Consult local plumbing & electrical codes. Identify all parts before assembling.
Parts List: The following parts are needed for pump installation.
Caution: Do not over-tighten fitting. Pump head will crack!
Checking Head Pressure:
Setting & Securing ARV Setting:
Parts List:
Parts List:
Parts List:
NOTE: DO NOT PLUG MAXI-VENT INTO CONSTANT HOT ELECTRICAL SOURCE. The Maxi-Vent will release water and any excess air/gas while the Air Pump is introducing air. Once the air reaches the base of the vent distributor tube in the vent tank, the air pocket is full. Air will begin to enter the vent distributor tube and exit the Maxi-Vent to drain. This will continue until the Air Pump and Maxi-Vent are deactivated.
Using the ball valve on the Maxi-Vent
The brass ball valve will be used as a shut-off for cleaning and servicing. It is also used to regulate the flow of air and water. Recommended flow regulation is usually between 0.5gpm and 2.0 gpm.
Using a flow switch with the Maxi-Vent
When using a flow switch to activate the air pump and Maxi-Vent, install after the vent tank and Maxi-Vent. If the flow switch is installed before the Maxi-vent, there will be a constant stream of water to the drain as the demand for water keeps the flow switch and air pump activated.
Note: Pump should be installed above the injection point. Compressed air will create condensate. Mounting above the injection point allows condensate to flow down toward injection point. This will help reduce moisture build-up from back flowing into Air Pump.
Note: Use caution; do not allow media to enter distributor tube.
Repeat step 11-13 to clear fines. Gently tapping sides of tank will help clear fines. Tap tank with rubber mallet while in backwash cycle. Monitor drain line to be sure mineral is not being backwashed out.
Note: When using Maxi-Vent with the Aer-Max System, higher ARV settings can be used. The Maxi-Vent expels air at a faster rate then a mechanical vent.
To adjust the Air Regulator Valve loosen lock nut (thin nut in the middle of fitting). Now the outer adjustment nut can be turned clockwise to increase pressure and airflow; or counter clockwise to reduce pressure and air flow during well pump cycle. If threaded out too far, air will flow freely out of regulator valve instead of pumping air into water line. Furthermore, if adjustment nut is removed, the check-ball and spring will fall out. If this happens, simply insert ball and spring and thread nut back in.
While the well pump and Air Pump are running you can set the Air Regulator Valve (ARV) to desired pressure. Start with ARV halfway open. As you turn adjustment nut clockwise, pressure will build in pump head. When pressure at head meets line pressure, air will be pushed into water line. When using the Maxi-Vent the recommended setting for the ARV is at the cut out pressure of the pressure switch.
To descrease or limit the introduction of air, set the ARV 5-10 pounds above the start up pressure of well pump. When the well pump starts up, the air pump also turns on, adding air during the beginning of pump cycle. Once the line pressure exceeds the setting on Air Pump ARV, no more air will be introduced into water line. The Air Pump will continue to run during the rest of the pump cycle but the excess air will be released out the ARV. (You should be able to hear or feel the air escaping.) If more air is desired, gradually set ARV to a higher pressure.
| Examples | ||
|---|---|---|
| Air Input | Well pump setting | ARV Setting |
| Minimum | 30 - 50 psi | 35 psi |
| Medium | 30 - 50 psi | 40 psi |
| Maximum * | 30 - 50 psi | 50 psi |
| * Maxi-Vent may allow for maximum ARV setting due to the high rate of air discharge. | ||
After setting ARV adjustment nut, secure lock nut to regulator body by rotating clockwise. This will lock the setting of the ARV. To re-adjust, loosen lock nut, reset adjustment nut, and secure lock nut. Follow up visits may be required to fine tune ARV.
We design Aer-Max Systems based on accurate water analysis and flow rates. Because we are unable to verify this information and we are unable to determine proper installation of equipment, we assume no liability for the determination of the proper equipment necessary to meet your requirements, and we do not authorize others to assume such obligations for us.
Air Pump Water Solutions, Inc. warranties its Aer-Max System as follows:
Fleck Controls: 3 year limited warranty
Structural Fiber Tanks: 10 years against rust and corrosion
Maxi-Vent: 1 year unlimited against manufacturer defects
Air Pump: 1 year from the date of manufacture unlimited warranty for defective materials or workmanship in manufacturing. This warranty covers replacement parts for the AP1 and AP2, as well as the cost of the labor to replace them when, proven to our satisfaction, that these parts are defective. Users of ozone may recieve full warranty on the Air Pump only when the compressor is "pushing" air into an ozone generator. The warranty is void when ozone is drawn through the Air Pump. This warranty is extended to the original purchaser at the original installation address when the pump is purchased from an authorized Air Pump Water Solutions, Inc. dealer.
Air Pump Water Solutions, Inc. assumes no responsibility for consequential damages, labor or expense as a result of any defect or failure due to circumstances beyond our control. Air Pump Water Solutions, Inc. will not be held liable for any fire damage, water damage, or damage to other water treatment equipment and plumbing due to malfunction of the Aer-Max System. Air Pump Water Solutions, Inc. has no control over misapplication or improper installation of the Aer-Max Systems, or improper installation of other water treatment devices.
The laws in your state may not allow limitation for responsibility for consequential damages, and this warranty may give you other legal rights that vary from state to state. Product improvements and design changes subject to change without notice.
After trying these possible solutions and your problem continues, you may call us toll free in USA and Canada at 1 877 4-AER-MAX (423 7629).
PROBLEM : Air spits and sputter from untreated lines. Possible cause is air is escaping from the aeration tank and is back flowing through the check valve, which may be installed in a horizontal position or has debris -- preventing check from sealing.
SOLUTION : Install check valve in a vertical position so that there is a column of water standing about a foot or more before the vent tank. See Section 3, Step 1.
PROBLEM : No air bubbles in water and discoloration returns. The cause may be a water logged vent tank or a mal-functioning A/P or no primary check valve ... See Solution #1, above.
SOLUTION : Run water in house and listen for splashing in vent tank, check #1 above and A/P. Plug A/P in alternate power source and observe pressure gauge on pump. ARV may have "drifted" to a lower pressure. See Section 2, Step 10, "Setting Head Pressure", to the cut out pressure.
PROBLEM : Water problems were initially solved but returned a few days later. Possible solution is a restriction in the backwash system.
SOLUTION : Make sure there is no kink in backwash line. Also, advance filter control to backwash and measure water flow from drain. A 5 gallon bucket will fill in one minute if there is no restriction. The flow may be restricted due to media lodged in the backwash chamber and/or backwash flow control button (washer). With water completely shut off, advance filter into backwash position. Use caution, unit may be still under pressure and may spray out water when drain line is removed. Remove locking pin where drain line is connected to filter. Remove fitting and clean out media. Re-connect and gradually open inlet valve to flush out excess mineral. Re-check flow rate from end of drain line.
PROBLEM : Low flow of water. Possible causes are A) a valve not opened fully, B) if the problem occurs a few weeks after initial installation, the filter media may be fouled with iron or sulfer bacteria. Examine bed, it may need to be stirred and backwashed again to remove fines.
SOLUTION : If bacteria is present, it will be necessary to modify the equipment. A chlorinator or other modification will solve the problem.
PROBLEM : No oder but discoloration is present. Possible causes are A) presence of tannins or colloidal iron or B) the filtering tanks are undersized.
SOLUTION : Aeration does not solve tannins and colloidal iron problems. Most filter media require twice the flow rate for backwashing then filtering. Higher flow rates may require two filter tanks in parallel in order for proper filtration. Well flow rate is determined by counting the gallons drawn down and the time between cut in and cut off cycle of the well pump. The formula for determining the flow rate is to measure the number of gallons drawn down, divided by the seconds required for recovery. Then, multiply result times 60 seconds.
PROBLEM : A/P does not build up pressure. Possible causes are A) the A/P may have been damaged during shipping and/or has a manufacturer's defect, B) check valves leaked water to the compressor, C) error performed in installation.
SOLUTION : Plug off the outlet of the compressor and plug into an alternate power source and observe pressure gauge. If the presuure does not come up to desired level, go to Section 1 and make certain that the fittings are installed in the exact ports shown in diagram 1. Except for small droplets on the poly tubing, there should be no water present. Test the 1/4 inch check valves if water is present in the tubing. They may need replacement. Be sure the A/P is mounted above the Level of the injection point. A damaged or defective A/P is rare. Please explore solutions before calling for a return authorization number.
PROBLEM : Sulfur odor is reduced, but not eliminated. Possible cause is that there is not enough turnover of air.
SOLUTION : Generally, hydrogen sulfide requires more air turnover than iron. Be certain that the ARV on the A/P is set at the maximum cut out level of the well pump.
This page consists mainly of installation pictures of the single-tank AER MAX aeration system with air pump and the Maxi-Vent electric ventilation system. (Other venting systems can be used.) It is intended to supplement manufacturers' instructions that are sent with the unit.
(Installation on top of a box not recommended.)
Important Note: The picture, for the photographer's convenience, shows the pump mounted below the level of the tank header assembly. It should be installed above the level of the tank top to avoid collection of moisture in the pump.
The 3/8" black tube at top is connected to the barbed tee provided to illustrate how it might be spliced into an existing filter backwash drain line. The tee, of course, is optional. The tube can be extended to any existing drain area. This tube will emit water while the well pump is running.
Electrically— the pump and the Maxi Vent operate only when the well pump is running and must therefore be wired into the well's pressure switch circuit
If your unit has double aeration, it will need something in each of the four holes shown.l
If it doesn't, hole (b) will be empty.
a. This is where the threaded plastic baffle is screwed in. This is the port where water to be treated enters.
b.
This is where the double aeration tube is screwed in. It is the port where air enters the tank. It will be left unused if your unit does not have the double aeration feature.
c.
The smaller unthreaded hole is where excess air is vented from the air tank. Push in the smaller diameter tube (the square-cut end goes into the hole).
d.
This is the port where treated water leaves the tank. Note that it has an O-Ring. Push the larger tube as far as it will go into the port.
(whole house & well units)
(listed by part numbers)